RP vs. Double Check vs. PVB: Which One Do You Need?

Side-by-side comparison of the common assembly types, the hazards each is approved for, and installation rules.

It comes down to what could get into the water. Anything that could make people sick calls for an RP. Lower-risk connections can use a double check. Irrigation often gets a PVB or SVB, which only protects against backsiphonage. Your district has the final say.

Side-by-side comparison

RP (RPZ)Double check (DC)PVB / SVB
Hazard levelHigh (health hazard)Low (non-health hazard)High or low, backsiphonage only
Protects againstBacksiphonage and backpressureBacksiphonage and backpressureBacksiphonage only
How it worksTwo checks with a relief valve between themTwo independent checksOne check plus an air inlet
Typical usesMedical/dental, restaurants, car washes, chemical-injection irrigation, industrialFire sprinkler services, some commercial and residential servicesLawn and landscape irrigation
Installation ruleAbove grade, never in a pit; relief valve needs drainageCan be below grade where allowed, with test accessAt least 12 in. above the highest downstream outlet
Discharges water?Yes, when relief valve opensNoPVB can spit at startup; SVB is designed not to

How to tell which one you have

  • RP: a relief port on the bottom between the two checks, usually with an air gap drain. Four test cocks.
  • Double check: two check valve bodies in line, four test cocks, no relief port.
  • PVB/SVB: a single body with a bonnet/canopy on top (the air inlet) and two test cocks, on an elevated riser.

Can I switch types?

Only with your water district's approval. Downgrading from RP to double check is rarely allowed. Upgrading is common when a property's use changes. We handle it under replacement or installation.

Testing differences

All of them get tested every year, just a little differently. On an RP we check the relief valve and both checks. On a double check we confirm each check holds. On a PVB we test the air inlet and the check. More on our testing page.

Related questions

Is an RPZ the same as an RP?

Yes. RPZ (reduced pressure zone) and RP (reduced pressure principle) refer to the same type of assembly.

How often does a backflow preventer need to be tested?

In California, backflow prevention assemblies must be tested at least once a year. They also need a test right after installation, after any repair, and after being moved. Your water district sets the exact due date and usually mails a notice before it.